    Applications
    Used in air conditioning units, elevator machine room, pumps, fans and other motor control applications, as protection of over-voltage, under voltage, phase failure, phase sequence, phase imbalance and PTC temperature. When the power supply is abnormal, turn off power supply to protect the equipment.
    Features:
    Built-in microprocessor, true RMS measurement, measurement accuracy≤1%. 50/64Hz universal, knob setting, LED indicator shows working status. Withe N-phase phase failure protection, unique load-side and PTC temperature protection, optional manual reset and key test function, DIN rail mounting.
    Model Description
    Model Selection Table
    ModelOver-voltageUnder-voltageUnbanlancePhase sequencePhase failure
    Setting rangeDelay rangeSetting range//
    Delay range
    ZHRV2-01——●●
    ZHRV2-02—-8%2s●●
    ZHRV2-031.05~1.300.1s~10s0.70~0.950.1s~10s—●
    ZHRV2-041.05~1.300.1s~10s0.70~0.950.1s~10s–●●
    ZHRV2-051.152s0.852s–●●
    ZHRV2-06—-5%~15%0.1s~10s●●
    ZHRV2-071.05~1.300.1s~10s0.70~0.950.1s~10s5%~15%0.1s~10s-●
    ZHRV2-081.05~1.300.1s~10s0.70~0.950.1s~10s5%~15%0.1s~10s●●
    ZHRV2-091.152s0.852s8%2s-●
    ZHRV2-101.152s0.852s8%2s●●
    ZHRV2-111.05~1.302s0.70~0.952s8%2s●●
    Note:
    1. “●”Function is available, “-“Function is not availble.
    Technical Parameters
    Rated supply voltageAC220V、AC230、AC240V、AC380V、AC400V、AC415V
    Rated supply frequency50Hz/60Hz
    Over-voltage threshold range(1.05~1030)×Ue
    Under-voltage threshold range(0.70~0.95) ×Ue
    Unbalance threshold range5%~15%
    Action delay range0.1s~10s
    Phase failure and phase sequence≤1s
    Voltage measurement error≤1%( Entire setting range)
    Delay error±10%+0.1s
    Knob setting accuracy±1% Scale value
    Rated insulation voltage415V
    Contact configuration capacity(A)10A
    IP ClassIP20
    Class of pollutionⅢ
    Electrical Life105
    Mechanical life106
    Altitude≤2000m
    Allowable relative humidity≤50%(40℃)( No condensation)
    Use categoryAC-15
    Short circuit protector typeRT36-00 5A
    Contact capacityUe/le:240V/1.5A,415V/0.95A
    Output type1C/O
    DIN rail Standard(width)35mm(IEC/EN60715)
    Function diagram

    Wiring Diagram
    Dimensions(mm)
    Ordering instructions
    Model significance:
    ZHRV2-02/A380 voltage relays, voltage AC 380V, with phase failure, phase sequence, unbalance protection, voltage unbalance rate 8%, action delay time 2s.Multi-function 3 Phase Voltage Relay Made in China
    website:http://www.cnakm.net/voltage-relay/multi-function-3-phase-voltage-relay/